General Routing Interface
The General Routing Interface General Routing interface Card is an optional module to provide fire routing outputs compliant with BS EN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1:2002 Applications / Limitations EN54-2 compliant routing interfaces providing monitored outputs to fire alarm and routing circuits. Circuits are monitored for open and short circuit conditions in both normal and active mode - compliance with EN54-2 and BS5839-1: 2002 Clause 12.2.1a The outputs will drive relay coils with impedances of between 1kΩ and 5kΩ. | Key Features
Order Codes and Options
CompatibilityCan be used with all MxPro 5 series control panels programmed with version 50.07 software or later, compatible with the PC-Configuration tool from version 6.12 or later. The interface connects directly to peripheral bus connection in the panel.
| ||||||||||||||||||||||||||
![]() | ![]() |