MxPro 4Peripheral Relay Card

The Peripheral Relay Card provides 10 30V DC, 1A programmable relay outputs.

The Peripheral Relay Card connects directly to any of the DIL connectors of either the Network Mimic 100 LED Output Card or the 50 way Input/Output Card unit via the supplied ribbon cable.

Each output follows the cause-and-effect programming of the mimic unit output.

This can be either a simple zone output or can be an individually programmed output group rule utilising the full range of features of the MxPro 4 dynamic zoning facilities.

Applications

These units can be used where many relay outputs are required for simple on/off signalling or control.

Key Features

  • Ten change-over contact outputs rated at 30V DC, 1A.
  • Up to 200 individual relay outputs fully programmable per mimic (excluding LEDs)
  • Ten individually programmable relay outputs per unit
  • DIN rail or screw fixing options
  • Separate isolate input (disables all outputs)
  • Separate isolate indication output
  • Fast response
Specification
Enclosure Dimensions H x W x D mmPCB: 90 x 160 x 15
Enclosure Dimensions H x W x D mmDIN rail: 90 x 160 x 40
DIN railModule mounts onto 32mm G Section and 35mm top hat (En50022) DIN rail
PCB Dimensions H x W x D mm35 x 142 x 70
Operating Temperature-5°C to 40°C
Relay Contacts10 volt free change over contacts
Contact Rating30V DC, 1A resistive
Power Supply (Card)24v DC nominal (21-28V DC)
Current (@24V DC)Quiescent: 0mA, relay on:13mA (per relay)
LED IndicationRelay circuit on (per relay)
Disable Control InputsVolt free input and mimic output drive option
Disable IndicationOpen collector output

Order Codes and Options

Mxp-052: 10 Way Relay Card
Mxp-046-DIN: 10 Way Relay Card in DIN Rail Carrier

Compatibility

Can be used with any of the network mimic units.

 

Advanced Fire Systems