MxPro 4Latch/Stretch Input Card

The Latch/Stretch Input Card provides monitoring for two momentary switch inputs. The module can be configured for Latch or Stretch modes of operation. The module can be configured for wiring supervision using the end-of-line resistor of the host input device. A reset input is provided for the reset of a latched condition.

Applications / Limitations

Can be used to monitor the operation of a momentary switched input that has been interfaced to the fire alarm control panel via loop devices or on-board inputs.

Two modes of operation are available for momentary switched operation, Latched or Stretched (30 Seconds).

Can be powered by a separate 24V DC supply, or loop powered.

Common reset input (volt free) allowing reset of the latched condition.

Key Features

  • Two modes of operation - Latched or Stretched
  • Monitored or Non-monitored connectivity
  • Loop powered
  • Configurable for Advanced, Apollo, Hochiki and Nittan input circuits
  • The module can be loop powered
  • 3 year warranty as standard
Specification
Applicable StandardsBS EN54-2; 1998, BS EN54-4: 1998
Relative Humidity-95% Non-condensing
Enclosure H x W x D mmPlastic ABS recyclable, 130 x 42 x20
DC Supply24V (17-28V) DC, 10mA
Input CircuitVolt free/end-of-Line 10K
Output CircuitVolt free/end-of-line 10K/20K,Max 30V DC
Reset Input CircuitVolt free
LED Indication4 x LED input active & wiring fault per input
Weight40 grams

Order Codes and Options

Mxp-053: Dual Input Latch/Stretch Module

Compatibility

Any volt-free switched input circuit.

End-of-line monitoring optional when used in conjunction with Advanced Electronics, Apollo, Hochiki or Nittan control equipment.

 

Advanced Fire Systems

Our fire panels and systems are known all over the world for their leading performance, flexibility and ease of installation and use.